The Gefran 800 V is a configurable controller for processes involving solenoid- and motorized valves. It is preferred in applications with limited space.
This instrument has up to 4 relay or logic outputs, 2 of which will be dedicated to the open/ close valve functions and up to 2 isolated analogic outputs, in voltage or current.
Every function is configurable from keyboard: available functions are control output (open/close valve); alarm output; timer controlled output; digital input repetition; retransmission of process value, setpoint, deviation, alarm setpoint or valvue read from digital communication.
- Universal input configurable from the faceplate
- Acquisition of the input signal every 120msec ; resolution 30000 steps
- 2 control outputs: relay, logic or analogue with open/ close valve function
- 3 configurable alarms
- 2 analogue outputs (setpoints retransmission)
- 2 digital inputs with configurable function
- Auxiliary input for valve position potentiometer feedback
- Heater Break or shortcircuit probe alarm
- Self and Auto- tuning , Soft- start, Local/ Remote, setpoint, Auto/ Man
- Multiset function, timer set ramp
Sensor Inputs: | |
Types: | |
TC- Thermocouples: | J, K, R, S, T, B, E, N, (NiNi18Mo), L-Gost, custom |
RTD 3-wires | Pt100 -200...850ºC JPt100 (JIS C 1609/81) -200...600ºC Custom -1999...9999 |
DC- Linear: | 0...50mV / 10...50mV / 0...20mA 4...20mA / 0...10V / 2...20V |
Auxiliary inputs: | (insulation 1500V) For remote setpoint: (0...10V, 2...10V, R = 1M?) (0...20mA, 4...20mA, Ri=5?); Valve position potentiometer feedback: >500? |
Logic: | Insulation 1500V NPN 24V/ 4.5mA (PNP 24V/ 3.6mA) Configurablefunction: Man/ Auto, Loc/ Rem, Alarms Reset, Hold, timer stop/ start/ reset, setpoint selection |
Sampling time: | 120 msec |
Precision: | Accuracy 0.2%f.s. ± 1 digit |
Digital input: | Optoisolated passive PNP isolated 1500 V |
Outputs: | |
Maximum number of outputs: | 5 |
Types: | |
Relay: | with rating: 5A/250V |
Logic: | 11Vdc, Rout = 220? (20mA, max. 6V) |
Analog: | 0...10V, 4...20 mA (Rmax = 500?) res. 12 bit not isolated Retransmission of variable |
Retransmission: | isolated 1500V |
Transmitter power supply: | isolated 1500V 10/24 Vdcmax. 30mA, short circuit protection |
Power supply: | Standard: 100...240 Vac/dc ± 10% on reqest: 20 to 27Vac/dc ± 10% 50/60 Hz; 8VA max. Protection by internal fuse not serviceable by the user |
Digital communication: | Non or RS485 / RS 232 |
Working temperature: | 0 to 50ºC |
![]() | |
Click here for more technical informations |