Gefran-Indicator-with-Alarm-I-300.JPG
Gefran I 300: Temperature & Humidity Indicator with Alarm
Stock Code:
SKU: product options

The Gefran I 300 two channel indicator / alarm unit is designed for combined measurement of temperature and humidity. It is used in food processing plants, water treatment and in chemical / pharmaceutical plants.

I 300 satisfies the demand for greater precision in measurement by thermocouples, resistance thermometers, linears and strain- gauges, with precision of 0.1%, 30.000 conversion points, and a full 5- digit display.The I 300 is equipped with to analogue inputs: the first can be configured to the thermocouple, resistance thermometers, even 3 or 4-wire, mV, V, mA, strain-gauge and variable resistance inputs; the second one can be selected among mV, V and mA inputs. These two inputs can be used as temperature and humidity or as differential.

Features:

  • 2 configurable inputs for differential (CH1-CH2) or temperature/ humidity measurement
  • Custom linearisation for the conversation into engineering units
  • Transmitter or sensor (strain gauge) power supply
  • Two configurable digital inputs
  • Isolated analogue retransmission
  • 4 configurable alarm points
  • 2- wire configurable optoisolated serial line. Protocol:  MODBUS or JBUS 

Sectors of Applications:

  • Food plants
  • Dryers
  • Chemical and pharmaceutical plants
  • Weighing
Sensor Inputs: 
Number of inputs:2
Types: 
Thermocouples:J, K, T, E, N, S, R, B, L, Ni-Ni18Mo, W Re 5/26
Resistance Thermometers:Pt 100 DIN43710 (3-wire), Pt 100 Japan, Ni100
Thermistors:--
Linear:0/4...20 mA, -20...20 mA, 0...50 mV, 10...50mV, -50...50mV, 0...100mV, 0...1 V, 0...10 V, Ri = 100K? for input 10 V; Ri = 2.5? for input mA; Ri > 1 M? for other inputs; Possible linearization on 25 segments
Sampling time:100 ms. current, voltage, RTD, ext. TC comp. input.
200ms. differential input; Ur/tºC; internal TC comp.
Precision:0.1% ± 1 digit
Digital input:2 inputs from voltage- free contact
Outputs: 
Maximum number of outputs:5
Types: 
Relay:4 configurable, max. 5 A, 250 V resistive load
Trip points, alarm
Logic:--
Analog:Resolut. 16000pti, precision 0.1%
0...10V, min 1K??; 0/4...20 mA max = 750?
Transmitter power supply:24 Vdc, max 50 mA, short circuit protection
strain gauge power supply 4,5...10,2V; max 30 mA
Power supply:100...240 Vac/dc; ± 10% 50/60 Hz
on request 24/48 Vac/dc ± 10% 50/60 Hz
Digital communication:RS485 2-wire (1200...19200 baud),
protocol MODBUS, JBUS
Faceplate protection level:IP 65
Working temperature:0 to 50ºC
 
Click here for more technical data
Below is a list of tags that have been applied to this product. Clicking on a tag will display a list of all products with that tag applied.