Self-tuning is an automatic procedure that calculates the best PID control parameters. Self-tuning may only be used when process is launched.
SETUP:
- Press and hold the  button until button until is displayed is displayed
- Using  buttons configure value to 99 buttons configure value to 99
- Press the  key once, key once, appears appears
- Using  buttons configure value to 128 buttons configure value to 128
- Press and hold the  button until button until is displayed is displayed
- Using  buttons configure value to 99 buttons configure value to 99
- Press  repeatedly until repeatedly until appears appears
- Using  buttons configure value to 6 buttons configure value to 6
- Press  repeatedly until repeatedly until appears; appears;
- Using  buttons configure value to 20 buttons configure value to 20
- Press and hold the  button until button until is displayed is displayed
- Press the  key once, key once, is displayed is displayed
- Using  buttons configure value to 2 buttons configure value to 2
- Press and hold the  button to return to the main screen button to return to the main screen
Press the  button to initiate self-tuning. LED 2
button to initiate self-tuning. LED 2  will flash whilst the controller calculates the control parameters and stops when the process is complete.
 will flash whilst the controller calculates the control parameters and stops when the process is complete.
**Note: self tuning may only be used when the process is launched (i.e from ambient, initial startup)

 
    
              

 
 