- A low temperature parallel resistance constant watt heat tracing cable
- Designed to provide frost heave protection of cryogenic storage vessels
- Cut-to-length parallel circuitry for field fabrication
- Fibreglass overlay
- Nominal watt density: 16-33 W/m
- Maximum Operating Voltage: 690 VAC
- Certifications/ Approval:
For a detailled quotation, please specify required W/m & quantity in metres, below.
Applications for Thermon FP parallel, Constant Watt Foundation Heating Cable
Thermon FP parallel resistance constant watt heating cables are designed to provide frost heave protection of cryogenic storage vessels.
With cut-to-length parallel circuitry, FP cables can be field fabricated, eliminating the need for specific circuit lengths to be provided for the application.
FP cable construction, with its unique fiberglass overlay, provides the needed cyclic reliability for foundation heating not found in other cables of this type. The fluoropolymer overjacket provides corrosion resistance, durability for installation in conduit, and lowers the friction factor for pulling. Because FP cables are not subject to the inrush current associated with self-regulating heating cables, the need for over sizing power distribution equipment is eliminated.
FP cables are certified for use in ordinary (nonclassified) areas and in potentially explosive atmospheres in accordance with the ATEX Directive and the IEC Ex Scheme.
Certifications/ Approvals
II 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67 T200°C to T85°C FM 07ATEX0016 | |
International Electrotechnical Commission IEC Certification Scheme for Explosive Atmospheres FMG 06.0008 | |
FM Approvals Ordinary and Hazardous (Classified) Locations | |
Underwriters Laboratories Inc. Hazardous (Classified) Locations |
Thermon FP Foundation Heating Cable has additional hazardous area approvals including:
• CCE/CMRS
- Nickel-plated copper bus wires 3.3 mm²
- Nichrome heating element
- Fiberglass overlay
- Fluoropolymer dielectric insulation
- Fluoropolymer dielectric Insulation.
- Fluoropolymer overjacket
Ratings
- Nominal watt density: 16-33 W/m
- Maximum operating voltage¹: 690 Vac
- Minimum installation temperature: -60°C
- Minimum bend radius
@ -15°C: 10 mm
@ -60°C: 19 mm - Pull strength: 500N
- Friction coefficient: 0.25-0.35
- Weight: 0.181 kg/m
Notes:
¹ | The 690 Vac maximum operating voltage applies to IEC Ex only. Max operating voltage for all other certifications is 575 Vac. |
Conventional Foundation Heating System
Power Output¹The rated power output of FP cables for voltages typically used in foundation heating is shown in the Table below. The heating zone length is the distance between bus wire connections.
Circuit Breaker Sizing and Circuit LengthMaximum current draws based on start-up temperatures are shown below. Circuit breaker sizing should be based on local regulations. Ground-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.
Notes:
| Power & End Termination KitFHT1-F-10 contains components to fabricate 10 power connections and 10 end terminations for FP foundation heating cable. (Components for a single circuit shown.) Kit includes:
Temperature ControlFrom both energy saving and operational standpoints, the heating system should include an effective and versatile temperature control system. Contact us for recommendations. |